Safety & protectionARD-SF-003
Flanged connectionFlanged flame arrester
Flanged
A flanged stainless steel flame-arrester range with published dimensional data through DN 250.
- Size
- DN 25–250
- Body material
- 06Cr19Ni10
- Connections
- Flanged
- Temperature
- −196 to +60°C
- Pressure
- PN16 (1.6 MPa nominal)
- Medium
- Specify process medium
Engineered for your application
A flanged stainless steel flame-arrester range with published dimensional data through DN 250.
Sizes and pressure ratings depend on construction, materials and configuration. Confirm the selected pressure-temperature rating with the quotation.
Technical data
The specification, in detail.
| Parameter | Technical specification |
|---|---|
| Size range | DN 25–250 |
| Pressure ratings | PN16 (1.6 MPa nominal) |
| End connections | Flanged |
| Published medium | IIC |
| Temperature range | -196 to +60°C |
Nominal pressure and ASME class are different rating systems. Confirm the pressure–temperature rating for the selected material and design.
End connections
Define the interface.
Shown configuration: Flanged protection device; this is not an isolation valve.
| Connection detail | Connection / selection requirement |
|---|---|
| Published connection | Flange(HG20592) |
| Referenced flange standard | HG 20592 (designation as published); edition, facing, drilling and pressure designation must be specified. |
| Flange selection | Specify nominal size, flange rating, facing, drilling and gasket. Do not infer these from the image alone. |
The illustration shows one configuration. Published connection alternatives are options for enquiry; their availability depends on size, rating, material and design. Installation dimensions come from the drawing, not the illustration.
Materials
From body to seal.
| Component | Material / option |
|---|---|
| Body | 06Cr19Ni10 |
| Core | 06Cr19Ni10 |
| Gasket | 06Cr19Ni10+graphite |
Published material alternatives are configuration-dependent. H.F. denotes hard facing; the exact grade and material certificates are confirmed with the offer.
Selection notes
Defined around your application.
- Flange(HG20592)
Sizes and pressure ratings depend on construction, materials and configuration. Confirm the selected pressure-temperature rating with the quotation.
“IIC” is the medium classification stated in the reference. The required gas group, flame-arresting duty and certification must be specified for selection.
Published ratings do not establish suitability for every listed medium. Oxygen cleaning, material compatibility, trapped-liquid relief and project approvals are specified for the selected assembly. Liquid-hydrogen and helium service require a separate temperature and material review.
Arden product datasheet
Product code ARD-SF-003 · Revision 2026-10-28. Product illustrations show one configuration; the approved order documentation defines the supplied assembly.
Download PDFDimensions
Plan the connection.
Dimensions apply to the tabulated version only. Confirm the approved outline drawing for the selected size, rating and connections before installation.
| DN | L | K | D | N-φ | Weight (kg) |
|---|---|---|---|---|---|
| 25 | 204 | 85 | 115 | 4-14 | — |
| 32 | 234 | 100 | 140 | 4-18 | — |
| 40 | 238 | 110 | 150 | 4-18 | — |
| 50 | 260 | 125 | 165 | 4-18 | — |
| 65 | 260 | 145 | 185 | 8-18 | — |
| 80 | 322 | 160 | 200 | 8-18 | — |
| 100 | 326 | 180 | 220 | 8-18 | — |
| 125 | 366 | 210 | 250 | 8-18 | — |
| 150 | 406 | 240 | 285 | 8-22 | — |
| 200 | 464 | 295 | 340 | 12-22 | — |
| 250 | 546 | 355 | 405 | 12-26 | — |
Linear dimensions are in mm and weights in kg unless stated otherwise. Pressure bands in MPa, thread designations and ISO mounting codes are not linear dimensions. Thread designations follow the reference. An em dash means no value is published. Confirm a certified outline drawing for the selected configuration.
Documentation
Product documents
Download the Arden data sheet for ARD-SF-003, or request the outline drawing for your selected configuration.
Product code ARD-SF-003 · Revision 2026-10-28. Illustrations show one configuration; approved order documentation defines the supplied assembly.